Đồng hồ đo điện trở vạn năng, Mega ôm mét, Fluke- Mỹ, Fluke 1587
Thông số kỹ thuật:
Hãng sản xuất: FLUKE- MỸ
Bảo hành: 12 Tháng
Voltage DC
Maximum Voltage: 1000 V
Accuracy: ±(0.2%+2)
Maximum Resolution: 0.001V
Voltage AC
Maximum Voltage: 1000 V
Accuracy: ±(2%+3)
Maximum Resolution: 0.1 mV
Current DC
Maximum Amps: 400mA
Amps Accuracy: ±(1.0%+2)
Maximum Resolution: 0.01 mA
Current AC
Maximum Amps: 400mA
Amps Accuracy: ±(2.0%+2) 1kHz bandwidth
Maximum Resolution: 0.01 mA
Resistance
Maximum Resistance: 50 MΩ
Accuracy: ±(1.2%+2)
Maximum Resolution: 0.1Ω
Insulation Test
Minimum Test Current @ 1kΩ/V: 1mA
Test Voltages: 500, 1000 V
Maximum Resistance per Test Voltage: 100V: 600 MΩ
Maximum Resolution per Test Voltage: 50V: 0.01 MΩ
100V: 0.01 MΩ
250V: 0.1 MΩ
500V: 0.1 MΩ
100V: 0.1 MΩ
Accuracy per Test Voltage: 50V: ±(3 % + 5)
100V: ±(3 % + 5)
250V: ±(1.5 % + 5)
500V: ±(2.0 % + 5)
100V: ±(2.0 % + 5)
Environmental Specifications
Operating temperature: –20 °C to +55 °C
Storage temperature: -40°C to +60°C
Humidity (Without Condensation): 0% – 95% (10 °C – 30 °C)
0% – 75% (30 °C – 40 °C)
0% – 40% (40 °C – 55 °C)
Operating Altitude: 2000 m
Safety Specifications
Overvoltage category: Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V
Agency Approvals: 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V
Mechanical & General Specifications
Size: 203 x 100 x 50 mm (with holster)
Weight: 624 g
Battery life Alkaline: Meter use 1000 hours
Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
IP Rating: IP40
Includes
Remote probe
Test leads
Alligator clips
Hard case
Four AA alkaline batteries
Quick Reference Guide
CD Rom with Manual
XEM ĐẦY ĐỦ
Bình luận.
Đánh giá